Overhead Distribution Cables
STANDARDS National : ICEA S-70-547
DESCRIPTION
CAHE Single Conductor Polyethylene-Covered Line Wire is rated for a 75°C normal conductor temperature, and is intended for use in overhead distribution circuits operating at primary or secondary voltages. The covering provides circuit protection against momentary contact with other conductors or trees. Because the covering carries no voltage rating, the conductors must be installed on insulators adequate for the intended service voltage. The user should consider the dielectric compatibility of the covering, insulator and conductor/insulator tie.
Conductor Construction
Conductors are available in the following constructions:
Aluminum conductor, steel reinforced (ACSR), concentric-lay stranded
Aluminum alloy 1350-H19 hard-drawn, concentric-lay stranded
Medium hard-drawn copper, solid or concentric-lay-stranded
Covering Material
The standard covering on the conductor is black linear low-density polyethylene (LLDPE). Alternatively, a covering of black low-density crosslinked polyethylene (XLPE) with a 90°C temperature rating is available upon request.
The LLDPE and XLPE coverings meet the requirements of ANSI/ICEA S-70-547-2007 (Standard for Weather-Resistant Polyethylene Covered Conductors).
Markings
The covering will bear the following surface markings:
Year and Plant of Manufacture
Conductor Size
Covering Material (LLDPE or XLPE)
standard
Overhead Covered Line Wire is manufactured and tested in accordance with ANSI/ICEA S-70-547 (Standard for Weather Resistant Polyethylene Covered Conductors).
LINE WIRE - ACSR CONDUCTOR
Code Word | Size (Stranding) | Covering Thickness (inch) | Cable | DC Resistance at 20°C (ohm/kft) | Inductive Reactance (ohm/kft) | Ampacity* |
Overall Diameter (inch) | Weight (lb/kft) | Breaking Strength (lbf) |
Walnut | 6 (6/1) | 0.030 | 0.26 | 45 | 1131 | 0.658 | 0.143 | 95 |
Butternut | 4 (6/1) | 0.030 | 0.31 | 70 | 1767 | 0.413 | 0.136 | 120 |
Pignut | 2 (6/1) | 0.045 | 0.41 | 115 | 2708 | 0.260 | 0.127 | 165 |
Chestnut | 1 (6/1) | 0.045 | 0.44 | 140 | 3373 | 0.206 | 0.122 | 190 |
Almond | 1/0 (6/1) | 0.060 | 0.52 | 185 | 4161 | 0.163 | 0.116 | 215 |
Pecan | 2/0 (6/1) | 0.060 | 0.57 | 225 | 5035 | 0.130 | 0.113 | 235 |
Cottonwood | 2/0 (6/1) | 0.080 | 0.61 | 240 | 5035 | 0.130 | 0.113 | 240 |
Filbert | 3/0 (6/1) | 0.060 | 0.62 | 275 | 6289 | 0.103 | 0.109 | 270 |
Buckeye | 4/0 (6/1) | 0.060 | 0.68 | 340 | 7933 | 0.0816 | 0.105 | 320 |
Gumwood | 4/0 (6/1) | 0.080 | 0.72 | 360 | 7933 | 0.0816 | 0.105 | 325 |
Hackberry | 266.8 (18/1) | 0.060 | 0.73 | 345 | 6555 | 0.0651 | 0.09 | 400 |
Redbud | 266.8 (18/1) | 0.080 | 0.77 | 365 | 6555 | 0.0651 | 0.09 | 400 |
Mockernut | 336.4 (18/1) | 0.060 | 0.81 | 425 | 8265 | 0.0516 | 0.087 | 460 |
Aspen** | 336.4 (18/1) | 0.080 | 0.85 | 445 | 8265 | 0.0516 | 0.087 | 465 |
For XLPE covering, add "XLP" to code word. (eg. Pignut/XLP)
* Ampacity based on conductor at 75°C, ambient temperature at 30°C, wind speed at 2 ft/s, with sun. For ampacity values at 90°C, contact our Sales Office. Inductive Reactance values are shown for 1.0 ft equivalent spacing. To correct Inductive Reactance in ohm/kft for other equivalent spacings (S) expressed in feet: XL= Value at 1.0 ft + 0.023 ln(S) For a frequency other than 60 Hz, multiply result by f/60 **This Code Word also refers to another product. To avoid confusion, we recommend specifying the size as well. |
|
LINE WIRE - ALUMINUM 1350 CONDUCTOR
Code Word | Size (# of wires) | Covering Thickness (inch) | Cable | DC Resistance at 20°C (ohm/kft) | Inductive Reactance (ohm/kft) | Ampacity* |
Overall Diameter (inch) | Weight (lb/kft) | Breaking Strength (lbf) |
Plum | 6 (7) | 0.030 | 0.24 | 35 | 507 | 0.661 | 0.118 | 95 |
Apricot | 4 (7) | 0.030 | 0.29 | 50 | 793 | 0.415 | 0.113 | 130 |
Peach | 2 (7) | 0.045 | 0.38 | 85 | 1215 | 0.261 | 0.107 | 170 |
Nectarine | 1 (7) | 0.045 | 0.42 | 105 | 1476 | 0.207 | 0.105 | 195 |
Quince | 1/0 (7) | 0.060 | 0.49 | 135 | 1791 | 0.164 | 0.102 | 225 |
Orange | 2/0 (7) | 0.060 | 0.54 | 165 | 2259 | 0.130 | 0.0994 | 260 |
Fig | 3/0 (7) | 0.060 | 0.59 | 200 | 2736 | 0.103 | 0.0968 | 300 |
Olive | 4/0 (7) | 0.060 | 0.64 | 245 | 3447 | 0.0820 | 0.0941 | 345 |
Pomegranate | 4/0 (19) | 0.060 | 0.65 | 245 | 3618 | 0.0820 | 0.0944 | 345 |
Mulberry | 266.8 (19) | 0.060 | 0.71 | 305 | 4473 | 0.0650 | 0.0915 | 410 |
Basswood | 300 (19) | 0.060 | 0.75 | 335 | 4932 | 0.0578 | 0.0901 | 430 |
Annona | 336.4 (19) | 0.060 | 0.79 | 375 | 5535 | 0.0516 | 0.0888 | 460 |
Molles | 397.5 (19) | 0.080 | 0.89 | 460 | 6399 | 0.0436 | 0.0869 | 510 |
Huckleberry | 477 (37) | 0.080 | 0.95 | 540 | 7821 | 0.0364 | 0.0845 | 585 |
For XLPE covering, add "XLP" to code word. (eg. Pomegranate/XLP) * Ampacity based on conductor at 75°C, ambient temperature at 30°C, wind speed at 2 ft/s, with sun. For ampacity values at 90°C, contact our Sales Office. Inductive Reactance values are shown for 1.0 ft equivalent spacing. To correct Inductive Reactance in ohm/kft for other equivalent spacings (S) expressed in feet: XL = Value at 1.0 ft + 0.023ln(S) For a frequency other than 60 Hz, multiply result by f/60 |
|
LINE WIRE - COPPER CONDUCTOR
Size (# of wires) | Covering Thickness (inch) | Cable | DC Resistance at 20°C (ohm/kft) | Inductive Reactance (ohm/kft) | Ampacity* |
Overall Diameter (inch) | Weight (lb/kft) | Breaking Strength (lbf) |
10 (1) | 0.030 | 0.16 | 35 | 390 | 1.03 | 0.131 | 55 |
8 (7) | 0.030 | 0.21 | 60 | 646 | 0.663 | 0.125 | 85 |
6 (7) | 0.030 | 0.24 | 90 | 1017 | 0.417 | 0.119 | 110 |
4 (7) | 0.030 | 0.29 | 140 | 1596 | 0.262 | 0.114 | 155 |
2 (7) | 0.045 | 0.38 | 225 | 2489 | 0.165 | 0.109 | 215 |
1 (7) | 0.045 | 0.42 | 280 | 3202 | 0.131 | 0.106 | 245 |
1/0 (7) | 0.060 | 0.49 | 360 | 4009 | 0.104 | 0.103 | 280 |
2/0 (7) | 0.060 | 0.54 | 450 | 5026 | 0.0822 | 0.100 | 325 |
3/0 (19) | 0.060 | 0.59 | 560 | 6308 | 0.0652 | 0.0968 | 380 |
4/0 (19) | 0.060 | 0.65 | 700 | 7904 | 0.0517 | 0.0942 | 440 |
250 (19) | 0.060 | 0.70 | 820 | 9870 | 0.0438 | 0.0922 | 490 |
350 (19) | 0.060 | 0.80 | 1140 | 13015 | 0.0313 | 0.0883 | 610 |
500 (37) | 0.080 | 0.97 | 1635 | 18525 | 0.0219 | 0.0839 | 770 |
* Ampacity based on conductor at 75°C, ambient temperature at 30°C, wind speed at 2 ft/s, with sun. For ampacity values at 90°C, contact our Sales Office. Inductive Reactance values are shown for 1.0 ft equivalent spacing. To correct Inductive Reactance in ohm/kft for other equivalent spacings (S) expressed in feet: XL = Value at 1.0 ft + 0.023ln(S) For a frequency other than 60 Hz, multiply result by f/60 |
Address:
No. 128, Tiancha Road, Economic Zone, Chuzhou, Anhui, China
Business Type:
Manufacturer/Factory, Trading Company, Group Corporation
Business Range:
Consumer Electronics, Electrical & Electronics, Industrial Equipment & Components, Instruments & Meters, Lights & Lighting, Manufacturing & Processing Machinery, Metallurgy, Mineral & Energy
Company Introduction:
China Anhui Electric Group Shares Co., Ltd. (CAHE) is a global company responsible for the production and distribution of wire and cable for the Energy Industry and to Electric Utilities responsible for power generation, transmission and distribution.
Our products include ABC Cable, ACSR, AAAC, AAC, ACSS, OPGW, Alumoweld, Galvanized Steel Wire, 15-35kV Copper and Aluminum Primary Distribution Power Cables, Secondary Aluminum and Copper 600V Service Drop and URD, 600V and 1kV Multi-conductor Control Cables, Bare Copper, Copper clad Steel, Industrial thermocouple, Industrial Thermal Resistance, Pressure Gauge Series, Bimetal thermometer, Paperless Recorder, Pressure transmitter, Temperature Transmitter, Intelligent Display Instrument, Level Meter / Flowmeter, Electrical equipment cable, Power cable, Bridge Series, Optical Fiber and Cable, Special cables, Special Thermocouple / Thermal Resistance and more.
CAHE makes it easier and less expensive as a complete solution for all cable needs. With inventory over $2 million in warehouses across P. R. China, we can solve immediate needs. Combined with our extensive manufacturing capability to ensure large project requirements, CAHE handles needs both large and small.
Our products are approved by CCC, AEIC, ICEA, ASTM, UL as applicable. (IEC, CSA, BS also available). CAHE is ISO 9001, 14001, 18000 certified.